Advantages
Air flow setting | Precise and independant setting of pressure |
Intake | For control and maintenance |
Possible use | Constant air flow |
Regenerations | Tested in laboratory (EN 7235) |
Dimensions
Min | 200 x 100 mm |
Max | 1000 x 1000 mm |
![](https://www.f2a.fr/wp-content/uploads/2018/09/Regulateur-a-debit-variable-rectangulaire-RRVS_F2A.png)
Characteristics
The RRVS damper is a slef-regulated system with adjustable air flow. It enables to control the air flow in a building’s zone according to specific instructions. Construction:
- Casing: galvanized steel or stainless steel 304L, 316L
- Blades: galvanized steel or stainless steel 304L, aluminium
- EPDM gaskets
Performance:
- Upstream/downstream airtightness: class 3 according to EN 1751
- Fram’s airtightness: class C according to EN 1751
- Air flow range: from 108 to 18 000 m3/h
- Operating temperature: -20 to +80°C
Options:
- Supply of a remote control for modifying the regulation range on site
- Actuators MPBUS, LON, MOD-BUS, BACNET
![](https://www.f2a.fr/wp-content/uploads/2018/09/Regulateur-a-debit-variable-rectangulaire-RRVS_F2A.png)