Rectangular dampers PLS

PLS

TECHNICAL DATA SHEET REGISTER TECHNICAL DATA SHEET REGISTER VERSION KIT [litebox id="boutonVoirVideo" href="#modalVideo" anch="PRESENTATION DU REGISTRE VERSION KIT" ]

Avantages

Upstream/downstream airtightness Class 3 (EN 1751)
Frame's airtightness Up to class C (EN 1751)
Large dimensions Up to 2000 x 1950 mm
Motorized version Available on request
Possible coupling External louver

Dimensions

Min 200 x 150 mm
Max 2000 x 1950 mm
L with a pitch of 100 mm
H with a pitch of 150 mm
Blades' height 150 mm
Frame's width 160 mm

Characteristics

PLS damper is designed to shut off large-sized ventilation networks. It is suitable for commercial HVAC applications.

Construction:

  • Frame and blades: galvanized or stainless  steel 304L
  • Lateral gaskets: stainless steel
  • Gaskets’ blades: EPDM
  • Control shift: Ø16 mm
  • Blades actuation via linkage
  • Manual or motorized control in factory

Performances:

  • Upstream/downstream airtightness: class 3 according to EN 1751
  • Frame’s airtightness: class A according to EN 1751
  • Acceptable pressure: 2 000 Pa for a length of L = 1m
  • Operating temperature: -20 to +80°C (+200°C in option)

In option:

  • Frame’s airtightness: class C according to EN 1751
  • Operating temperature up to +200°C
  • Painting

Your compare list

Compare
REMOVE ALL
COMPARE
0