BS 476 Part 20 / French Interministerial Circular No. 2000-63 / UL 555S
Up to 10000 Pa with 4-hour fire integrity and flame tightness following the ISO 834 fire curve at temperatures exceeding 1150°C
TRS
- Smoke damper



Description
The TRS smoke damper is designed for high-temperature smoke exhaust applications in tunnels, transport infrastructure, car parks, and industrial facilities. Compliant with BS 476 Part 20, it provides fire resistance and full operability at temperatures up to 400°C for 2 hours (250°C for 3 hours).
Thanks to its reinforced design and large free area, the TRS damper enables high-capacity and controlled smoke exhaust during fire events. It can be used as a tunnel smoke damper, fan isolation damper, or fire safety damper in industrial HVAC systems.
The TRS damper features a robust construction with a 3 mm welded frame, reinforced aerodynamic blades, high-temperature silicone seals, and multiple pneumatic or electric actuation configurations.
Characteristics
Type: Smoke damper
Function: Shut-off
Standards: BS 476 Part 20 / French Interministerial Circular No. 2000-63 / UL 555S
Minimum size: W 200 × H 250 mm
Maximum size: W 2500 × H 2500 mm
Blade airtightness: Class 3 according to EN 1751
Casing airtightness: ATC3 according to EN 1751 (formerly Class C)
Maximum operating pressure: 10,000 Pa
Maximum air velocity: 25 m/s
Fire resistance rating: 400°C / 2h and 250°C / 3h
Materials: Galvanized steel or stainless steel
Actuation: Manual or motorized (electric or pneumatic)
Performances:
Airtightness
TRS: Class 3 according to EN 1751
TRS-T: Class 3 according to EN 1751 + certified in accordance with French Interministerial Circular No. 2000-63
Certifications
BS 476 Part 20
UL 555S
Integrity and flame tightness maintained for 4 hours following the ISO 834 fire curve at temperatures exceeding 1,150°C
Pressure rating
The TRS damper is designed to withstand differential pressures of up to 10,000 Pa with a 1,250 mm blade length in the galvanized steel version.
Fire resistance rating
250°C for 3 hours
400°C for 2 hours
Full operability maintained throughout the test
Applications
Road tunnels
Railway tunnels
Metro systems
Underground car parks
Industrial smoke exhaust systems
Fan isolation
Fire safety systems
High-pressure ventilation systems
Critical industrial installations
Emergency ventilation systems
BS 476 Part 20 / French Interministerial Circular No. 2000-63 / UL 555S
Up to 10000 Pa with 4-hour fire integrity and flame tightness following the ISO 834 fire curve at temperatures exceeding 1150°C
Technical datasheet of TRS damper
Need help?
Need help finding the right solution for your needs?
Our teams are available Monday to Thursday from 8 a.m. to 5:30 p.m. and Friday from 8 a.m. to 4:30 p.m.