Effectively prevents air backflow in HVAC systems while ensuring excellent leakage control
Stainless steel, ATEX and high-temperature options up to +200°C
AR
- industrial backdraught damper


Description
The ARO / ARE industrial backdraught dampers are designed to automatically prevent air backflow in industrial ventilation systems. Operating by gravity, the blades open under the effect of the airflow and automatically close when the airflow reverses, ensuring one-way air circulation.
Thanks to their robust industrial design, high resistance to back pressure, and wide choice of materials (stainless steel, aluminium, ATEX), ARO / ARE dampers are ideally suited to demanding industrial applications.
Available in galvanized steel, stainless steel, aluminium, or painted steel, they meet the requirements of ventilation systems exposed to high mechanical loads and harsh operating environments.
Thanks to their modular design, AR dampers can be easily installed in rectangular ductwork for commercial buildings, technical rooms, and industrial facilities.
Characteristics
Type
- Industrial backdraught damper
Function
- Prevent air backflow
Dimensions
- Minimum size: W200 × H180 mm
- Maximum size: W1500 × H1500 mm
Airtightness
- Blade leakage: Unclassified to Class 3 in accordance with EN 1751
- Casing airtightness: ATC4 / ATC3 in accordance with EN 1751 (formerly Class B and C)
Maximum operating pressure
- 3000 Pa
Recommended air velocity
- 5 to 15 m/s
Airflow direction
- Horizontal / Vertical
Operating temperature range
- -20°C to +80°C (-50°C to +200°C available)
Materials
- Galvanized steel
- Stainless steel
- Aluminium
Performances
Airtightness
- ARO: Unclassified
- ARE: Class 3 in accordance with EN 1751
Pressure
- The AR backdraught damper range is designed to withstand operating pressures up to 3000 Pa with an 800 mm blade length in the galvanized steel version
Operating temperature range
- Standard: -20°C to +80°C
- Option: -50°C to +200°C
ATEX
- Certified for installation in ATEX zones
Applications
- Industrial HVAC systems
- Industrial ventilation systems
- Exhaust systems
- Offshore installations
- Petrochemical industry
- Technical rooms
- Smoke exhaust systems
- Process ventilation
- ATEX installations
- Nuclear facilities
Effectively prevents air backflow in HVAC systems while ensuring excellent leakage control
Stainless steel, ATEX and high-temperature options up to +200°C
Need help?
Need help finding the right solution for your needs?
Our teams are available Monday to Thursday from 8 a.m. to 5:30 p.m. and Friday from 8 a.m. to 4:30 p.m.