TECHNICAL DATA SHEET REGISTER
TECHNICAL DATA SHEET REGISTER VERSION KIT
[litebox id="boutonVoirVideo" href="#modalVideo" anch="PRESENTATION DU REGISTRE VERSION KIT" ]
Advantages
Upstream/downstream airtightness | Class 1 (EN 1751) |
Frame's airtightness | Up to class C (EN 1751) |
Time limit | 72h ex works for standards dimensions |
Motorized version | Available on request |
Dimensions
Min | 100 x 100 mm |
Max | 1400 x 1400 mm |
L with a pitch of | 50 mm |
H with a pitch of | 50 mm |
Blades's height | 100 mm |
Frame's width | 130 mm |
Characteristics
Rectangular dampers – U range
The shut off damper UWG is designed to isolate ventilation networks in commercial buildings.
U damper exists in volume control version (UWO) and Airitght version class 1 (UWS)
Construction:
- Frame: galvanized steel, stainless steel or aluminium (frame’s width of 110mm only)
- Blades: galvanised steel
- Lateral gaskets: stainless steel
- Blades’s gaskets : EPDM
- Control shaft 12mm
- Blades actuation with linkage (UWG) or with gear wheels (ULG)
- Manual or motorized control at the factory
Performances:
- Upstream/downstream: class 1 according to EN 1751
- Frame’s airtightness: class A according to EN 1751
- Acceptable pressure: 1 000 Pa for a length of L = 1m
- Operating temperature : -20 to +80°C
Options:
- Frame’s airtightness : class B or class C according to EN 1751 to reduce leakage rate in ventilation networks
- Painting
Available in kit version
The kit version damper is delivered in spare parts and is equipped with a new mounting system including angle pieces
Blades, top/bottom and sides are available in four dimensions :
• 400 mm
• 600 mm
• 900 mm
• 1200 mm
Those elements can be cut at your required dimensions.