Advantages
Certified | According to EN 12101-8 (CE marking), EN 1366-10 |
Structure | Single-compartment |
Tests | According to EN 1366-10 (600°C/2h) |
Upstream/downstream airtightness | Class 3 (EN 1751) |
Large dimensions | 2000 x 1995 mm |
Motorized | With Bernard actuator AQ10 (100 Nm), Belimo BE230 or BE24 |
Dimensions
Min | 200 x 180 mm |
Max | 2000 x 1995 mm |
L with a pitch of | 100 mm |
H with a pitch of | 165 mm |
Blades' height | 165 mm |
Frame's width | 300 mm or 185 mm |
Features
Smoke exhaust dampers prevent the spread of smoke and combustion products from a fire zone, but they are also used to hold toxic extinguishing gas from the critical area and control excessive air exhaust in pressurization systems. Smoke control systems are designed to fulfill the following basic functions:
- extraction of smoke from a single fire compartment to the outside of the building
- extraction of smoke from fire compartments of a building, using a smoke and heat extraction system
The smoke exhaust damper MSD-F has been tested and certified according to EN 12101-8 (CE marking). It complies with EN 13501-4 classification standard and 1366-10 test standard. It meets European requirements for single-compartment applications. It is equipped with an electric actuator AQ10 and a thermal jacket.
Certification number: 1812-CPR-1180_17-0 (Effectis laboratory)
Certificate of compliance (Qatar): EFR-1702-0038_17-0
MSD-F classification according to EN 13501-4:
Construction :
- Frame and blades: galvanized or stainless steel
- Blades’ gasket: silicone and graphite
- Lateral gasket: graphite
- Motorized drive system
Performances :
- Upstream/downstream airtightness: class 3 according to EN 1751
- Acceptable pressure: -500 Pa to +500 Pa
- Operating temperatures: 600°C/2h certified